High Inlet Temperature Air Dryer

High Inlet Temperature Air Dryer up to 60℃

Contact Now

Product Parameters

PSI High Inlet Temperature Compressed Air Dryer:

• Maximum 14 barg operational pressure

• Ambient temperature up to 50°C.

• Inlet air temperature up to 60°C.

• R407C environmentally friendly refrigerant in all models.


Product selection


ModelAir Flow Rate

Air ConnectionPower SupplyRefrigerant TypeDimmensions (mm)Weight(kg)
NM³/MinLWH
PFD72T1.2Rc 1/2"230V/1Ph/50HzR134a65032055035
PFD144T2.4Rc 1"230V/1Ph/50HzR134a80042060070
PFD180T3.0Rc 1"230V/1Ph/50HzR134a80042060075
PFD360T6.0Rc 1 1/2" 230V/1Ph/50HzR407C7506951260125
PFD480T8.0Rc 1 1/2"230V/1Ph/50HzR407C7506951260128
PFD600T10.0Rc 1 1/2"230V/1Ph/50HzR407C7506951260133
PFD720T12.0Rc 2"230V/1Ph/50HzR407C10008401450165
PFD900T15.0Rc 2"230V/1Ph/50HzR407C10008401450175

Norminal dryer flow rated at inlet pressure 7 barg, inlet air temperature 60℃,ambient temperature 38℃ and dew point 3℃ to 10℃.


Technique info

How to select a suitable PSI High Inlet Temperature Dryer

Correction factor for pressure barg (CP)

3456789101112131415
0.74 0.83 0.90 0.93 1.00 1.04 1.08 1.11 1.15 1.18 1.22 1.25 1.28 


Correction factor for inlet air temperature (CT)

50℃55℃60℃65℃70℃75℃80℃
1.03 1.02 1.00 0.87 0.78 0.70 0.64 


Correction factor for ambient temperature (CA)

25℃30℃35℃38℃40℃45℃50℃
1.15 1.10 1.02 1.00 0.890.790.69


  1. Selected the correction factor(CP),(CT) and (CA).

  2. Calculate the dryer capacity require using the following: Actual flow rate=Nominal flow rate x CP x CT x CA